Dimensions
Charms and Controller Enclosures:
800mm (W) x 2000mm (H) (+100mm plinth) x 600mm (D)
800mm (W) x 2000mm (H) (+100mm plinth) x 800mm (D)
Traditional IO Enclosures:
800mm (W) x 2000mm (H) (+100mm plinth) x 800mm (D)
1200mm (W) x 2000mm (H) (+100mm plinth) x 800mm (D)
1600mm (W) x 2000mm (H) (+100mm plinth) x 800mm (D)
Data Enclosures:
800mm (W) x 2000mm (H) (+100mm plinth) x 800mm (D)
800mm (W) x 2000mm (H) (+100mm plinth) x 1000mm (D)
800mm (W) x 2000mm (H) x 1200mm (D)
Access
Front Access – Single Door, Right Hand Hinged, Push Button and Lock Insert
Front and Rear Access – Single Door on Front and Rear, Right Hand Hinged, Push Button and Lock Insert
Front and Rear Access – Double Door on Front and Rear, Push Button and Lock Insert
Protection Category
IP 54 – Type 12
Weight
~200 kg (may vary as per hardware added by option selection)
Material
Enclosure Frame : Sheet Steel, 1.5 mm, Dipcoat-primed,
Door: Sheet Steel, 2 mm, Dipcoat-primed, Powder-coated on the Outside, Textured Paint,
Color: RAL 7035, Plinth RAL 9005
Door fans
Continuous run or with thermostat control
Power Requirements
Internal Power Distribution
Redundant distribution through Main Switch:
100-120 VAC 50/60 Hz
220-240 VAC 50/60 Hz
24 V DC
Configured with one of the following internal power supply systems:
2 x 20A and full redundant (primary and secondary) 24 VDC distribution
2 x 40A and full redundant (primary and secondary) 24 VDC distribution
Control Network
Redundant Copper (RJ45)
IO Count / Type
DeltaV DCS Charms Encosures:
Up to 504 IO AC powered CIOC
Up to 576 IO DC powered CIOC
Controller Encosures:
Up to 288 CHARMS IO
DCS - CIOC with Non IS, IS IO Charms
SIS-CSLS with Non IS, IS IO Charms
Traditional IO DCS Encosures:
M Series DeltaV Conventioal IO Hardware
S Series DeltaV Conventioal IO Hardware
Non IS Traditional IO Cards
Date Enclosures:
Network Enclosure
Server/ Network Enclosure
Name Plate
Name Plate Holder with Nameplate Insert
Environmental Specification
Indoor installation
Equipment Room - HVAC Controlled, Recommended temperature 25° C
IT Room- Recommended temperature 20° C
Relative humidity
5-95% (non-condensing)
Globally Certified
Europe: CE
North America: Ordinary Location